Adiabatic protective conductor calculator
Calculate the adiabatic conductor cross-section from fault current, duration and a documented k coefficient. See fault energy without a compliance verdict.
United Kingdom · Choose an edition
Calculation method
Supply k for the actual conductor, insulation and initial/final temperatures. The model is limited to fault durations of 0.001–5 seconds.
For the installation context behind these inputs, read Earthing system types: TN-S, TN-C-S and TT.
Continue the calculation with Cable voltage drop calculator.
Method and assumptions
- I²t assumes constant RMS fault current over the duration. For current-limiting devices use manufacturer let-through data separately. Mechanical minima, connections and disconnection conditions still require assessment.